§ 23.25.1207.2. Temporary gas installations—Permit required.  


Latest version.
  • Amend section 1207 by adding a new section 1207.2 as follows:

    1207.2 Temporary gas installations - permit required.

    A.

    Temporary gas approval is given to allow "comfort heating" appliances to be used to provide temporary heat to a building or building site prior to the completion of the building's primary heating system.

    B.

    The most commonly used appliance is a natural gas portable space heater. Other comfort heat appliances allowed for temporary heat purposes are warm air furnaces, boilers, and unit heaters. It is NOT the policy of the Building Safety Division or Enstar Natural Gas Company to allow "decorator fireplaces" or "ranges" to be utilized as temporary heat for buildings. These appliances are not designed or "listed" for such purpose.

    C.

    All appliances used to provide temporary heat for buildings shall be installed in accordance with the manufacturers' instructions and terms of their listing, with particular attention being paid to the clearances to combustibles from the top, bottom, back, and sides of these appliances.

    D.

    Unit heaters used for temporary heat shall be installed per manufacturers' instructions and listed clearances to combustibles from the top, bottom, front, back, and sides of these appliances. The vent connector shall be graded at one-quarter inch (1/4") per foot slope upward to the outside and it shall be changed to "B" vent at the wall penetration. The "B" vent must maintain its listed clearance to combustibles, extend a minimum of five (5) feet vertically, and be secured.

    E.

    Furnaces used for temporary heat shall comply with the same requirements as for unit heaters as stated above. In addition, the return air for the furnace shall be ducted a minimum of ten (10) feet from the furnace.

    F.

    Portable space heaters shall be provided with one hundred percent (100%) outside air to the back end of the heater. In most cases, the gas regulator attached to these heaters shall be piped to the outside. If the regulator vent discharges, it shall not be allowed to discharge into the space being heated.

    G.

    Gas hose used for temporary heaters shall be a type approved by the Building Safety Division and all manufacturers' listed clearances shall be maintained. The hose shall have an internal wire mesh or braid and be "kink proof". Supporting wire shall run the full length of the hose. Each time a hose is moved from one lot to another, it shall be retested with sixty (60) psi air pressure.

( AO No. 2015-127, § 1, 4-1-16 )