§ 23.25.815.0. Soda fountains, condensates, drip pans, ice machines, and other similar equipment.  


Latest version.
  • Add new section as follows:

    815.0 Soda fountains, condensates, drip pans, ice machines, and other similar equipment.

    A.

    If the drain outlet for this type of equipment is below or remotely located from an approved point of disposal, the equipment may drain by gravity to a single pump, lift station receiver based on the following:

    1.

    A "Little Giant" condensate unit or equal is acceptable for lift station receiver. The pump shall be appropriately sized for the required condition.

    2.

    The equipment drain outlet or tailpiece may not exceed 1" I.D.

    3.

    The discharge pipe and fittings from the lift station receiver shall be a material approved for drainage piping and shall be piped to an approved indirect waste receptor per Uniform Plumbing Code section 701.

    B.

    Vending company employees may install the drainage piping from the equipment they install to an approved point of disposal, provided the equipment drain pipe from the outlet of the tailpiece to a lift station receiver or approved point of disposal does not exceed five (5) feet measured along the centerline of the pipe and such piping is installed in accordance with the Uniform Plumbing Code requirements.

    C.

    If the equipment installed requires a water supply, it shall be provided by a properly licensed plumber to within ten (10) feet of the equipment, complete with any required backflow prevention device. The vendor employee may make the water connection from that point to the equipment.

( AO No. 2015-127, § 1, 4-1-16 )