§ 23.25.603.5.10. Steam or hot water boilers.
Amend section 603.5.10 as follows:
603.5.10 Steam or hot water boilers. Potable water connections to hot water boilers shall be protected from backflow by a minimum double check valve with intermediate vent backflow prevention assembly complying with ASSE 1012. Potable water connections to steam boilers shall be protected from backflow by a minimum reduced pressure principle backflow prevention assembly in accordance with Table 603.2. Where chemicals are introduced into the system a reduced pressure principle backflow prevention assembly shall be provided in accordance with Table 603.2.