§ 23.25.1210.5.2. Medium pressure gas.  


Latest version.
  • Add a new section as follows:

    1210.5.2.1 Medium pressure gas. The installation of a medium pressure gas system (2 psig or 5 psig) within a building must be pre-approved by the local gas utility. Steel piping shall be welded. Test pressure for all medium pressure gas piping shall be 60 psig.

    Exception: Medium pressure gas piping within mechanical room spaces that house the equipment being served shall be threaded or welded in accordance with 1208.5.8. Threaded piping shall not be concealed within the space.

    1210.5.2.2 CSST medium pressure gas. The installation of a CSST medium pressure gas system (2 psig or 5 psig) within a building must be preapproved by the local gas utility. Test pressure for all medium pressure gas piping shall be 60 psig. Joints shall be limited to the meter connection and at the regulator to the appliance being served. Intermediate joints are not allowed without prior approval.

( AO No. 2015-127, § 1, 4-1-16 )