§ 23.75.2.2.6. Stop switch in pits.  


Latest version.
  • In 2.2.6-Stop Switch in Pits, amend by adding the following paragraph to the end of subsection 2.2.6.2:

    The pit stop switch required at approximately 450 mm (18 in.) above the floor level of the landing shall be permitted to be mounted between 40 in. and 60 in. above the floor level of the landing, adjacent to the pit ladder. If this is done, then a second pit stop switch shall be mounted in the pit adjacent to the pit ladder approximately 1 200 mm (47 in.) above the pit floor.

( AO No. 2015-127, § 1, 4-1-16 )