§ 23.30.210.23. Permissible loads, multiple-outlet branch circuits (outlets per circuit).  


Latest version.
  • Add subsection (E) as follows:

    (E) Outlets per circuit. In dwelling units, no more than thirteen (13) outlets are allowed on one branch circuit. All smoke detectors on a circuit may be counted as a total of one outlet. Appliance circuits are limited to six (6) duplex receptacles per circuit.

    Exception: Fixed lighting circuits designed to meet the appropriate sections of the code.

( AO No. 2015-127, § 1, 4-1-16 )